IAT-HD

60–2,500 A and 1,500–15,000 V


IAT-HD Digital Medium Voltage Autotransformer

Advantages at a glance

  • Up to 50°C ambient temperature
  • Comprehensive motor protection and control package
  • IP 41 as standard, up to IP65 optional
  • Advanced electronic potential transformer utilizing patent pending “wireless” voltage measurement system
  • Wide 50 – 60Hz range
  • Engineering included
  • Closed control circuit by current measurement, Back-up via time control
  • Innovative low voltage test – testing of complete function
  • Nominal voltage test – option
  • Optic data logging
  • Real-Time-Clock

Details

For full view please move the table horizontally if necessary.
System Voltage Current Motor Dimensions Weight
kV A kW HP W (mm) H (mm) D (mm) kg
2.3 60–2,500 170–5,400 230–7,200 1,100–1,300 2,300 1,200–1,500 800–1,500
3.3 60–2,500 250–7,700 340–10,300 1,100–1,300 2,300 1,200–1,500 850–1,550
4.16 60–2,500 320–9,200 430–13,000 1,100–1,300 2,300 1,200–1,500 850–1,850
6.0 60–2,500 540–14,000 730–18,500 1,200–1,500 2,300 1,400–1,800 950–1,950
6.6 60–2,500 600–15,500 810–20,500 1,200–1,500 2,300 1,400–1,800 950–1,950
10.0 60–2,500 910–23,000 1,230–30,500 1,400–3,500 2,300 1,400–2,200 2,300–4,500
11.0 60–2,500 1,000–25,500 1,350–34,000 1,400–3,500 2,300 1,400–2,200 2,100–4,500
13.8 60–2,500 1,260–31,500 1,700–42,000 1,600–4,200 2,300 1,500–2,400 2,800–5,000
15.0 60–2,500 1,370–35,000 1,850–46,500 1,600–4,200 2,300 1,500–2,400 3,150–6,000

Approvals

1) Case by case

Digital

  • Illuminated LCD with 2 lines of 16 characters each
  • Selectable languages: English, German, French or Spanish (aditional on request)
  • The LCD indicates the motor current, fault descriptions and statistical data.
  • The LEDs provide a quick status indication. (control voltage on, motor start, motor on, motor stop, fault)
  • Easy settings by six clearly marked keys, user-friendly software with factory default parameters.

Communication RS 485

Modbus Profibus

RS 485 with MODBUS or PROFIBUS protocol enable:

  • Remote (start, stop, etc.)
  • Monitoring (motor current, faults, statistical data)
  • Remote parameter setting
  • Remote reset

Bypass

Internal bypass

  • This reliable components bypass autotransformer after the motor is at speed.
  • In addition the starters provide an auxiliary contact, allowing signaling of a successful motor start.
    Attention! Many of our competitors call these auxiliary relays “a bypass contact”!
  • The bypass function reduces the heat dissipation and eliminates the EMC load of the system.